Sustainability Audit Report Submitted: May 4, 2009 Audit performed by: Dustin Quandt Space/Date Audited: Alumni Center, 3/31/2009 Building contact: Christi Kasten This report contains observations of the CH2M Hill Alumni Center and recommendations to enable building occupants to make their workspace and processes more sustainable. These recommendations aim to respect the unique nature of each space while encouraging occupants to make changes that will reduce environmental impacts. If you have any questions or comments regarding the report format, observations or recommendations, please write to sustainability@oregonstate.edu. Other departments interested in a sustainability audit can contact the email above. Recommendation Summary Table 1. Recommended and Potential Energy Conservation MeasuresReturn on Annual Energy Annual Cost Implementation Conservation Measure Investment Savings Savings ($) Cost(years)Replace all incandescent lights with CFLs. Avg. $5/bulb; 7,925 kWh $396.23 0.8Estimated impact is 51 lamps. $255 totalInstall occupancy sensor to reduce lighting hours 640 kWh $32.00 $94.00 2.9in breakroom. Estimated impact is 8 fixtures.Outdoor lighting off during daylight hours 6,570 kWh $328.50 $380.00 1.2Turn off or standby computers at night that typically run 24/7; estimated impact is 15 9,765 kWh $488.25 $0.00 ImmediatecomputersEnable standby modes on computers that typically run during working hours; estimated impact is 20 ...
-