Sustainability Audit Report Submitted: November 13, 2008 Audit performed by: Kelsey Fisher Space/Date Audited: Surplus/October 16, 2008 Building contact: Pete Lepre Lighting Observations: Typical fixtures are 4 lamp T8 fluorescent hanging, and 2 lamp T8 fluorescent recessed with opaque shield type diffusers. Lights were mostly off in unoccupied areas. Some bulbs were out in the warehouse. Lighting Energy Usage Fixture Type Quantity Energy use per fixture Watts per fixture type 1 lamp T12 1 34W 34 4 lamp T8 40 128W 5210 2 lamp T8 40 64W 2560 300W incandescent 2 300W 600 Recommendations: Replace all incandescent and halogen bulbs with compact fluorescent (CFL) bulbs. CFLs produce light much more efficiently than incandescent and halogen bulbs. CFLs also produce less heat, an important factor to consider during the summer months. CFLs come in a wide-range of spectra and intensities, so a suitable CFL can be found for almost any application. Replace or remove burnt-out fluorescent lamps. Unlike incandescent bulbs, burnt-out fluorescents still consume energy. If the light level in the area is adequate without the lamp lit, please email sustainability@oregonstate.edu for more information on delamping procedures. If the lamp has been out for more than two weeks and needs to be replaced, contact Facilities Services by email at FacilitiesCustomerServ@oregonstate.edu or by phone at 7-2969. Notes on specific areas with ...
-